Current Transducer 0-10A DC In, 0-10V DC Out, DIN Mount

Converts DC input current into a load independent output signal DC 0-10V. Can be used for monitoring the current in motor winding and with the 0-10V can be easily interfaced to our modules analog inputs. The current transducer features total galvanic isolation between input/output, high accuracy, low drifting by temperature, and wide temperature operational range.

Description

Converts DC input current into a load independent output signal DC 0-10V. Can be used for monitoring the current in motor winding and with the 0-10V can be easily interfaced to our modules analog inputs. The current transducer features total galvanic isolation between input/output, high accuracy, low drifting by temperature, and wide temperature operational range.

Specifications

  • Input current: 0 to 10A DC
  • Output voltage: 0 to 10V DC
  • Power supply voltage: 24V DC (+/- 5%)
  • Accuracy @IPN, TA=25°C: 0.5%
  • Minimum input current for linear measurements: 20% of the maximum input range
  • Response Time: < 350ms
  • Current consumption: <35mA
  • Measured impedance: <500Ω
  • Zero offset  , TA=25°C: 0.08mA
  • Operating temperature: -25..+70 °C
  • Storage temperature: -50..+85 °C
  • Mounting: DIN RAIL
  • Dielectric strength: 3kV (50 Hz / 1 min)